2 Hour Rated Pipe Collar
Application:
Service penetrations – plastic SWD systems
Fire Resistance Period:
120 minutes, depending upon the application.
Insulation/integrity:
Insulati
Test Standard:
BS EN 1366-3, CE Mark 2812 – CPR-EA5002, ETA 20/1207
Pyroplex® 200 Series Slimline Pipe Collars have been specifically designed to reinstate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. The slimline fire collar will seal closed flammable pipes from a 50mm to 160mm diameter and can be face fixed to a wall or ceiling structure suitable for use on concrete, masonry and plasterboard partitions. Tested in accordance with EN1366-3, achieving a fire resistance period of up to 120 minutes (depending upon the application), classified in accordance with BS EN 1366-3, CE Mark 2812 – CPR-EA5002, ETA 20/1207
Main Features
Pyroplex 200 Series SL Pipe Collars have achieved a fire resistance of up to 120 minutes.
Pyroplex 200 Series SL Pipe Collars have a zintec coated steel outer casing.
Embossed for identification and traceability purposes.
Tab closing device means the collars are easy to fix in place around the pipe and rotate or slide into position.
Intumescent material is totally unaffected by water, is robust, ‘non-flaking’ and difficult to tear.
Field of Application
Pyroplex 200 Series SL Pipe Collars have been specifically designed to prevent the passage of fire and hot gases through:
Concrete and masonry constructions – Suitable for plasterboard partitions 55mm to 160mm
Soil, waste, and drainage ‘above ground’ applications
Suitable for plastic flammable pipes with PVC-C, PVC-U, PE, PP, ABS and SAN+PVC pipes